基于有效值滑窗差分算子和采样序列重构的电压暂降测量方法
DOI:
作者:
作者单位:

1.湖南师范大学工程与设计学院;2.湖南大学电气与信息工程学院

作者简介:

通讯作者:

中图分类号:

TM930.1

基金项目:

国家自然科学基金项目(面上项目,重点项目,重大项目)、湖南省自然科学基金


Voltage sag measurement method based on RMS sliding window difference operator and sampling sequence reconstruction
Author:
Affiliation:

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    电压暂降是电力系统中最令用户困扰的电能质量问题,对其特征参数进行准确测量是电压暂降评估和治理的首要前提。然而,当前电压暂降检测算法存在参数检测准确度低、实时性差以及缺乏相位跳变信息等不足。为此,文中提出一种基于有效值滑窗差分算子和采样序列重构的电压暂降测量方法,以实现其特征参数的快速、准确检测。该方法首先利用有效值滑窗差分算子准确获取电压暂降的起止时刻。接下来,依据暂降起止时刻对原始信号分区,并对不同分区的信号进行加窗插值FFT运算。而后,对采样序列重构并进行相位校正。最后,得到电压暂降的持续时间、暂降深度和相位跳变等特征参数信息。在暂降幅值和相位同时变化、不同谐波分量、不同信噪比噪声等情况下的仿真实验结果表明,文中所提方法具有准确度高、实时性好和鲁棒性强等优点。实际构建硬件测试平台的测试结果满足GB/T 30137-2013中电压幅值误差≤0.2%、相位跳变误差≤1°以及暂降持续时间误差不超过一个周期的要求,验证了算法的有效性和可行性。

    Abstract:

    Voltage sag is one of the most perplexing power quality problems in power system. Accurate measurement of its characteristic parameters is the primary premise of voltage sag evaluation and management. However, the current voltage sag detection algorithm has some shortcomings, such as low accuracy of parameters detection, poor real-time performance and lack of phase-angle jumps. Therefore, a new method of voltage sag measurement based on RMS sliding window difference operator and sampling sequence reconstruction is proposed in this paper to achieve fast and accurate detection of characteristic parameters. Firstly, the RMS sliding window difference operator is used to obtain the initial and end time of voltage sag. Next, the original signal is partitioned according to the initial and end time of the voltage sag, and the window interpolation FFT algorithm is performed on the signals in different sections. Then, the sampling sequence is reconstructed and the phase is corrected. Finally, characteristic parameters are calculated, such as the duration of voltage sag, depth of voltage sag and voltage phase-angle jumps. The simulation results under the conditions of simultaneous change of value and phase, different harmonic components and different SNR noise show that the proposed method has the advantages of high accuracy, excellent real-time performance and strong robustness. The test results of the actual hardware test platform meet the requirements of GB/T 30137-2013, such as relative error of voltage amplitude and absolute error of phase-angle jumps are less than 0.2% and 1°, respectively, and absolute error of duration of voltage sag is less than one cycle, which further verifies the effectiveness and feasibility of the proposed algorithm.

    参考文献
    相似文献
    引证文献
引用本文
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2024-03-29
  • 最后修改日期:2024-05-29
  • 录用日期:2024-05-29
  • 在线发布日期:
  • 出版日期: